Lodestar CL2B

Fault Locator Lodestar CL HV
blinking_dest_2.png
Fault Locator Lodestar CL HV
Fault Locator Lodestar CL HV
Lodestar CL4 set
Fault Locator Lodestar CL HV

INQUIRY NOW

Technical specifications

PARAMETER VALUE
Operating parameters
Types of registered events
  • PtP faults
  • PtG faults
  • transient faults
Operating voltage, kV
  • 6-36
  • 36-70 (option with Faraday cage)
Operating current, A 0-1000
Operating frequency, Hz 50/60
Conductor size 5-40 mm / 19,6-1256 mm²
Fault sensing
Detection of earth fault direction -
Absolute threshold, A 20 A÷1000
Differential thresholds 20 А÷500 A / 50%÷500%
Minimum fault sensing (PtG)
Zero sequence current thresholds/3I0, A
2-100
Response time, ms 20
Fault notification
Visual ultra bright LED (white):
  • ≥ 100 m – day time
  • ≥ 500 m – night time
Resistance
Current withstand, kA/ms 25/500
In-rush resistance, ms 0-200 /step 20
Communication
Short-range communication technology built-in BLE module, 50 m
On-site configuration and control Mobile App Lodestar (Android, iOS)
Long-distance communication pole-mounted communication box (GSM)
Fault management software KOMORSAN
Reset
By timer, hour 1-72 (configurable)
Remote Lodestar App, KOMORSAN, SCADA
Reenergized line by voltage
Manual magnet
Physical characteristics
Dimensions, mm 140 x 114 x 158
Weight, kg 0.55 
Housing UV resistant polycarbonate
Ambient conditions
Temperature range, °C from – 40 to + 85
IP protection IP68
Salty fog resistant (IEC 60068-2-11)
Installation
Installation tools
  • dielectric rod
  • Lodestar hotstick tool adaptor
Installation method Live line
Battery
Battery type and capacity lithium, 3.6 V
Battery life time >1000 h, >7 years
Low battery alarm at 20 % of remaining battery load:
  • visual by LED blinking (yellow color)
  • KOMORSAN notification
Other
Applicable standards ANSI / IEEE 495
Internal memory 20 000 events
Measured telemetry parameters
  • current
  • voltage absence/presence

*Only for isolated neutral grounding. Min 5 km behind FPIs is required.

 

Lodestar CL2B was designed especially for medium voltage utility overhead lines. It ensures 99% accuracy of detection of load currents from 2A. CL2B is provided with current and voltage unique measurement algorithms and outstanding fault detection capabilities. Three devices Lodestar CL2B located on different phases of the line perform synchronous vector measurements.

In the event of a fault on an overhead line, the indicators flash using ultra-bright LEDs, with the flashing pattern corresponding to the specific fault type. To enable data transmission from the devices to the KOMORSAN data collection server or to the dispatcher’s SCADA system, the devices can be equipped with the Lodestar Smartbox or Lightbox data transmission unit. 

Lodestar CL2B benefits:

  • Versatile installation – independent of conductor configuration and number of circuits.
  • Secure attachment – reliable clamp for firm mounting on the conductor.
  • Hot‑stick installation – easy mounting without de‑energizing the line.
  • Flexible SCADA integration – IEC 60870‑5‑104 via KOMORSAN software or direct DNP3 connection using a communication unit.
  • Directional fault detection – identifies fault current direction.
  • Any neutral grounding type – effective operation in any neutral grounding arrangement.
  • Versatile network compatibility – suitable for radial and looped networks with single or multiple feeds.

 

 

Documentation is provided upon request to the company's clients. Please fill in the form to send a request:

+

By sending this form, I consent to the processing of my personal data.

Reliable and efficient operation of power line networks depends significantly on rapid detection and localization of faults. Atriy’s advanced short circuit indicator solutions are designed precisely for this crucial task, ensuring fast troubleshooting on cable power lines and substations.

Essential Features and Applications

Atriy provides a robust short circuit sensor capable of swiftly detecting both phase-to-phase and earth faults. The indicators can precisely locate faults in underground and overhead cable networks, significantly reducing downtime and associated maintenance costs. Effective in multi-phase systems, these devices reliably pinpoint issues, enabling quicker response time and improving overall service continuity.

Main advantages:

  • Immediate detection and clear indication of fault locations
  • Effective in multi-phase power systems
  • Easy integration with existing SCADA systems
  • Robust construction for harsh environmental conditions
  • Minimal maintenance requirements

Atriy’s indicators significantly improve operational efficiency by quickly pinpointing faults, thus reducing service interruptions and repair time. This capability is essential in densely populated or critical infrastructure areas, where rapid restoration is vital.

Comprehensive Fault Management Solutions

Atriy’s circuit indicator power lines solutions provide:

  • Rapid response and reduced downtime
  • Decreased operational and maintenance costs
  • Enhanced reliability of cable networks

Integrating advanced technology, these indicators ensure swift fault localization, minimizing interruptions and ensuring the highest reliability standards.

Why Choose Atriy Fault Indicators?

  • Fast Fault Detection: Immediate identification shortens troubleshooting significantly.
  • Cost-Effective Maintenance: Reduced resources for manual fault identification.
  • High Reliability: Proven effectiveness even under severe conditions.

Choose Atriy's cutting-edge solutions to enhance your power grid reliability and minimize downtime, ensuring continuous and efficient operation of your power infrastructure.