Lodestar FM-FL

Lodestar FM

INQUIRY NOW

Technical characteristics of Lodestar FM-FLx system

PARAMETER

Lodestar
FM-FL HV

Lodestar
FM-FL

Lodestar
FM-FL +

 Mains voltage level, kV 230   6-36 
 Mains frequency, Hz  from 45 Hz to 65  
Recorded fault types
 Identification of single-phase faults +
 Identification of two-phase and three-phase faults +
 Determination of two-phase and three-phase faults direction +
 Direction determination for phase-to-phase and three-phase faults involving ground +
 Identification of single-phase PtG +
 Determination of single-phase PtG direction +
 Selectivity  determination of short-circuit faults direction  determination of single-phase PtG, short-circuit faults direction 
 Fault location determination

   with an accuracy of ±300 m

KOMORSAN software implementing a fault location mechanism

Power supply
 Supply from any of the following control voltages:
  • 220 V DC, 110 V DC, or 220 V AC mains supply
  • 12 V DC backup power supply 
 Fault indication reset
  • external command
  • by timer
  • by the front panel button 
General description of devices
 Visual fault indication
  • LED indication
  • LCD indicator
 Minimum zero-sequence current for single-phase PtG registration, А  - 0.5   -
 Fault detection during line switch-on +
 Number of latest faults stored in the internal memory 240
 Communication
  • RS-485 Modbus protocol
  • Ethernet IEC 608 70-5-104 protocol   
 Operation monitoring
  • visual
  • relay output
  • RS-485
  • Ethernet
  
 Changing settings
  • via USB using client software
  • via the device menu
  • remotely via GSM using software
  • KOMORSAN Web Client
 Integration with SCADA systems
  • via the KOMORSAN software
  • when the Lodestar FM-FL + is connected to the Lodestar KL Smartbox
  • directly to the SCADA system using the IEC 60870-5-104 protocol 
  
 Recording
  • voltage
  • current power
  • power frequency
  • three-phase power factor
  • power flow direction
  • minimum and maximum power flow values   
 Measurement accuracy
  • voltage 1%
  • current 1%
  • active, reactive and apparent power 1 %
  • frequency 1% 
  • voltage:
    • with 3% accuracy capacitive dividers
    • when using voltage transformers with an accuracy of 1%
  • current 1%
  • active, reactive and apparent power 5%
  • frequency 1%  
 Mounting switchboard panel    into a switchgear cell, on a control panel
Connection
  • current sensor (current transformers)
  • voltage transformer
  • current sensor (current transformers)
  • standard voltage transformer
  • capacitive divider
  • current sensor Rogowski coil
  • standard voltage transformer
  • capacitive divider
Operating temperature range, °С from –40 to +70
 IP rating of the feeder monitor    IP 20

 

Now it is possible to detect simply the fault localization on overhead and cable power lines with the new universal device Lodestar FM-FL. Such ultra-compact device, mounted easily in the switchgear, monitors the network status constantly and determines the damage location with accuracy of 300 meters. Working in networks with any type of neutral, Lodestar FM-FL Fault Location System records any type of emergency situations on cable and overhead distribution line.

For switchgear that are not equipped with their own current sensors, it is recommended to install Lodestar FM-FL with current sensors based on the Rogowski coil, which is installed in substations where standard current transformers are not planned, mounted or required.

The intelligent feeder monitor analyzes a wide range of parameters and displays on-line the characteristics of current, power, voltage, etc., as well as minimum and maximum values of flow.

Lodestar FM-FL is available to order in three modifications depending on the voltage class and current sensors:

  • Lodestar FM-FL+ voltage class 6-36 kV with Rogowski coils;
  • Lodestar FM-FL voltage class 6-36 kV with current transformer sensors SCTххх;
  • Lodestar FM-FL HV voltage class up to 230 kV with current transformer sensors SCTххх.

Benefits:

  • Multiple configurations – wide range of versions for different network requirements.
  • Continuous network monitoring – real‑time network status awareness.
  • Geographic fault visualization – exact fault location displayed on a map.
  • High‑accuracy fault location – determines fault location with ±300 m accuracy for long-distance lines.
  • Comprehensive fault recording – records all types of faults.
  • Flexible SCADA integration – supports IEC 60870‑5‑104 over Ethernet; Modbus over RS‑485.

Documentation is provided upon request to the company's clients. Please fill in the form to send a request:

+