Feeder monitor Lodestar FM - cable fault locator or fault indicator | ATRIY
 +971 555-998-004

Lodestar FM

Lodestar FM

INQUIRY NOW

Technical specifications

PARAMETER VALUE
Mains voltage level, kV 6-230
with standard current transformers
Recorded fault types
Identification of two-phase and three-phase faults +
Identification of single-phase PtG +
Determination of singlephase PtG direction +
Fault detection on line switch-on (single-phase PtG, PtP) +
Minimum zero-sequence current for single-phase PtG registration), А 0.5
General description of devices
Visual fault indication
  • LED indication
  • LCD indicator
Power supply
AC or DC supply voltage, V 110/220
or ~220
External backup power supply, V -
Communication interface
  • RS-485
  • Ethernet
Communication protocol
  • Modbus
  • IEC 608 70-5-104
Operation monitoring
  • visual
  • relay output
  • RS-485
Measurement accuracy
 Current, % 1
Voltage, % 1
Active, reactive and apparent power,% 3
Frequency, % 1
Mounting
 Mounting  switchboard mounting
External transducer
 Сurrent sensor standard current transformers
Voltage transformer (VT)
  • standard voltage transformer
  • capacitive divider
Operating temperature range, °С from –40 to +70
IP rating of the feeder monitor IP 60

 

The Lodestar FM feeder monitor is a universal device for recording and analyzing fault events. It combines selective line fault detection in networks of any topology and neutral grounding type with the measurement of key power parameters on 6-230 kV overhead and cable lines of distribution networks using standard current transformers (CTs).

 Benefits:

  • High‑sensitivity earth fault recording – detects earth faults down to 0.5 A.
  • Power system automation – automation functions for distribution networks.
  • Non‑volatile memory – retains data and settings during power loss.
  • Intelligent network monitoring – real‑time monitoring with advanced analytics.
  • Faulted section visibility – clear fault location in any network topology and neutral grounding type.
  • Universal sensor compatibility – standard CTs/VTs, dedicated CTs, capacitive voltage dividers.
  • Flexible communication – relay output and RS‑485 (Modbus RTU) for SCADA integration.