Lodestar CL4B | ATRIY
 +971 555-998-004

Lodestar CL4B

Fault Locator Lodestar CL4
blinking_2.png
Fault Locator Lodestar CL4
Fault Locator Lodestar CL4
Lodestar CL4 set

INQUIRY NOW

Technical specifications

PARAMETER VALUE
Operating parameters
Types of registered events
  • PtP faults
  • PtG faults
  • transient faults
Operating voltage, kV
  • 6-36
  • 36-70 (option with Faraday cage)
Operating current, A 0-1000
Operating frequency, Hz 50/60
Conductor size 5-40 mm / 19,6-1256 mm²
Fault sensing
Detection of earth fault direction -
Absolute threshold, A 20 A÷1000
Differential thresholds 20 А÷500 A / 50%÷500%
Minimum fault sensing (PtG)
Zero sequence current thresholds/3I0, A
4-200
Response time, ms 20
Fault notification
Visual ultra bright LED (white):
  • ≥ 100 m – day time
  • ≥ 500 m – night time
Resistance
Current withstand, kA/ms 25/500
In-rush resistance, ms 0-200 /step 20
Communication
Short-range communication technology built-in BLE module, 50 m
On-site configuration and control Mobile App Lodestar (Android, iOS)
Long-distance communication pole-mounted communication box (GSM)
Fault management software KOMORSAN
Reset
By timer, hour 1-72 (configurable)
Remote Lodestar App, KOMORSAN, SCADA
Reenergized line by voltage
Manual magnet
Physical characteristics
Dimensions, mm 140 x 114 x 158
Weight, kg 0.55 
Housing UV resistant polycarbonate
Ambient conditions
Temperature range, °C from – 40 to + 85
IP protection IP68
Salty fog resistant (IEC 60068-2-11)
Installation
Installation tools
  • dielectric rod
  • Lodestar hotstick tool adaptor
Installation method Live line
Battery
Battery type and capacity lithium, 3.6 V
Battery life time >1000 h, >7 years
Low battery alarm at 20 % of remaining battery load:
  • visual by LED blinking (yellow color)
  • KOMORSAN notification
Other
Applicable standards ANSI / IEEE 495
Internal memory 20 000 events
Measured telemetry parameters
  • current
  • voltage absence/presence

*Only for isolated neutral grounding. Min 5 km behind FPIs is required.

 

Lodestar CL4B was designed for fault detection with minimum load current 4A. This is a cost-effective and reliable solution.

In the event of a fault on an overhead line, the indicators flash using ultra-bright LEDs, with the flashing pattern corresponding to the specific fault type. To enable data transmission from the devices to the KOMORSAN data collection server or to the dispatcher’s SCADA system, the devices can be equipped with the Lodestar Smartbox or Lightbox data transmission unit. 

Lodestar CL4B benefits:

  • Versatile installation – independent of conductor configuration and number of circuits.
  • Secure attachment – reliable clamp for firm mounting on the conductor.
  • Hot‑stick installation – easy mounting without de‑energizing the line.
  • Flexible SCADA integration – IEC 60870‑5‑104 via KOMORSAN software or direct DNP3 connection using a communication unit.
  • Directional fault detection – identifies fault current direction.
  • Any neutral grounding type – effective operation in any neutral grounding arrangement.
  • Versatile network compatibility – suitable for radial and looped networks with single or multiple feeds.

 

Documentation is provided upon request to the company's clients. Please fill in the form to send a request:

+

By sending this form, I consent to the processing of my personal data.



عملائنا

Contact Us

  Iris Bay 21st Floor, Office # 2105-2108, Business Bay, Dubai, UAE

 

  +971 555-998-004

Get Product Updates