Feeder Monitors for substation installation: Lodestar FM-DFI | ATRIY
 +971 555-998-004

Lodestar FM-DFI

INQUIRY NOW

Technical characteristics of Lodestar FM-DFI

PARAMETER VALUE
Mains voltage level, kV 6-36
Recorded fault types
Identification of two-phase and three-phase faults +
Identification of single-phase PtG +
Determination of singlephase PtG direction +
Fault detection on line switch-on (single-phase PtG, PtP) +
Minimum zero-sequence current for single-phase PtG registration), А 0.5
General description of devices
Visual fault indication
  • LED indication
  • LCD indicator
Power supply
AC or DC supply voltage, V 100-240
or ~100-270
External backup power supply, V -
Communication interface
  • RS-485
  • Ethernet
Communication protocol
  • Modbus
  • IEC 608 70-5-104
Operation monitoring
  • visual
  • relay output
  • RS-485
  • Ethernet
Measurement accuracy
 Current, % 3
Voltage, %
  • 1 when using a voltage transformer (VT)
  • 3 when using capacitive dividers
Active, reactive and apparent power,% 3
Frequency, % 1
Mounting
 Mounting switchboard mounting / wall-mounting
External transducer
 Сurrent sensor

Rogowski coil 3 to 30 in multiples of 3

Voltage transformer (VT)
  • standard voltage transformer
  • capacitive divider
Operating temperature range, °С from –40 to +70
IP rating of the feeder monitor IP 60

 

Lodestar FM-DFI is a universal device for registration and analysis of emergency processes that combines the functions of selective detection of line damage in networks of any topology and type of neutral and measurement of basic parameters of electricity. The Device is designed to detect the fact and determine the direction of phase-tophase short-circuits, phase-to-ground fault in overhead and cable power distribution lines of 6-36 kV. Lodestar FM-DFI monitors the minimum voltage and extra voltage with indication of alarm signals.

Benefits:

  • Directional fault detection – detects and identifies the direction of occurred earth faults.
  • Flexible power supply – auxiliary power, line supply, or constant voltage.
  • High measurement accuracy – precise fault detection and monitoring.
  • Flexible SCADA integration – supports IEC 60870‑5‑104 over Ethernet; Modbus over RS‑485.
  • Large event memory – stores more than 200 fault events for post‑fault analysis.

 

Documentation is provided upon request to the company's clients. Please fill in the form to send a request:

+

By sending this form, I consent to the processing of my personal data.



عملائنا

Contact Us

  Iris Bay 21st Floor, Office # 2105-2108, Business Bay, Dubai, UAE

 

  +971 555-998-004

Get Product Updates